TERMIUM Plus®

The Government of Canada’s terminology and linguistic data bank.

POISON TANK [1 record]

Record 1 2008-11-21

English

Subject field(s)
  • Nuclear Power Stations
CONT

This was a fast-acting liquid poison injection system comprising a number of small tanks containing gadolinium nitrate solution which were connected to perforated Zircaloy in-core injection tubes. The top of each poison tank was connected to high pressure helium storage tanks via an array of valves which were opened on a trip signal, thereby pressurizing the poison solution and causing it to flow rapidly into the perforated in-core tubes and, hence, into the bulk moderator.