Record 1 2000-04-28

English

Subject field(s)
  • Burners and Steamfitting
  • Ovens, Furnaces and Boilers (Heating)
DEF

An interlock which proves the damper is open for prepurge.

CONT

At startup, terminal 3 is energized, powering the blower motor through terminal M. The blower pressure switch contact closes, completing the interlock circuit between terminals 3 and P when blower pressure reaches 16 in. water column. Terminal X is powered to position the choke valve in its high fire position, with the high fire interlock satisfied via a jumper between terminals 3 and 10. (It is noted that the choke valve is normally open during this part of the sequence due to the way the valve motor is connected to the controller). The programmed sequence is now initiated. The Blower and Purge LED indicators on the Fireye controller will light.

Key term(s)
  • high-fire interlock

French

Domaine(s)
  • Fumisterie et brûleurs
  • Fours et chaudières (Chauffage)
OBS

Voir la fiche «puissance maximale d'utilisation; allure maximale / high fire».

Spanish

Save record 1

Copyright notice for the TERMIUM Plus® data bank

© Public Services and Procurement Canada, 2024
TERMIUM Plus®, the Government of Canada's terminology and linguistic data bank
A product of the Translation Bureau

Features

Language Portal of Canada

Access a collection of Canadian resources on all aspects of English and French, including quizzes.

Writing tools

The Language Portal’s writing tools have a new look! Easy to consult, they give you access to a wealth of information that will help you write better in English and French.

Glossaries and vocabularies

Access Translation Bureau glossaries and vocabularies.

Date Modified: