Fiche 1 2010-07-22

Anglais

Subject field(s)
  • Pumps
  • Heating
DEF

A pump for exhausting air [or steam] or other as from an enclosed space to a desired degree of vacuum.

CONT

These same basic components may be used in the design of a vacuum or a subatmospheric system. The vacuum heating pump maintains a vacuum in the return piping under all operating conditions, assisting the supply steam in overcoming the resistance of the system piping and assuring rapid and uniform steam distribution.

CONT

Vacuum pumps are used on a system where the returns are under a vacuum. The assembly consists of a receiver, separating tank and automatic controls for discharging the condensate to the boiler. Vacuum pumps are sized in the same manner as condensate pumps for a delivery of 2.5 to 3 times the design condensing rate.

Français

Domaine(s)
  • Pompes
  • Chauffage
CONT

Chauffage à pression sous-atmosphérique. [...] Les pompes à vide sont de deux sortes : 1. les pompes à piston, activées par la vapeur, aspirantes et foulantes, et, 2. les pompes centrifuges accouplées directement à un moteur électrique.

CONT

Chauffage à vapeur sous vide. Une pompe à vide permet d'obtenir dans l'installation une pression inférieure à la pression atmosphérique [...] Le vide est parfois réalisé à l'aide d'une pompe refoulant l'eau condensée dans la chaudière et munie d'un système d'injecteurs appropriés [...]

CONT

Pour les grands édifices [...] il est difficile de placer tous les échangeurs de chaleur au-dessus du niveau d'eau du générateur ou de la tuyauterie de retour. On utilise dans ce cas une pompe à vide qui maintient une pression inférieure à la pression atmosphérique (jusqu'à 650 mm de Hg) dans la tuyauterie générale de retour [...]

Espagnol

Conserver la fiche 1

Fiche 2 2007-10-17

Anglais

Subject field(s)
  • Pumps
  • Heating
CONT

Figure 2 depicts a two-pipe vacuum heating system which uses a condensation pump as a mechanical lift for system where a part of the heating system is below the boiler room.

OBS

Compare with diffusion pump.

Français

Domaine(s)
  • Pompes
  • Chauffage
OBS

Comparer avec pompe à vide à diffusion.

Espagnol

Campo(s) temático(s)
  • Bombas
  • Calefacción
Conserver la fiche 2

Fiche 3 1992-05-12

Anglais

Subject field(s)
  • Food Preservation and Canning
CONT

Exhausting includes the removal of air from the filled can and the establishment of conditions whereby the finished canned product will show a substantial degree of vacuum. This can be done by heating the filled can in steam or hot water for several minutes so that the air is driven out and the temperature of the contents is raised considerably. It can also be accomplished by a vacuum closing machine where the air is sucked out by a pump and the lid is sealed on while the suction is being maintained.

Français

Domaine(s)
  • Conservation des aliments et conserverie
CONT

Le préchauffage est l'opération qui consiste à porter le contenu des récipients présertis à une température d'environ 70-80 degrés Celsius pendant quelques minutes. (...) Le préchauffage a pour rôle essentiel d'éliminer l'air inclus dans les cellules des fruits, dans le jus et dans l'espace libre situé entre le produit et le couvercle de fermeture.

Espagnol

Conserver la fiche 3

Fiche 4 1990-01-29

Anglais

Subject field(s)
  • Pumps
  • Heating
CONT

Condensate return pumps are used for low pressure, gravity return heating system. They are normally of the motor driven centrifugal type and have a receiver and automatic float control. Other types of condensate return pumps are the rotary, screw, turbine and reciprocating pump. ... the condensate pump has a capacity of 2.5 to 3 times normal flow.

CONT

When the steam condensate cannot be returned by gravity to the boiler in a two-pipe [steam heating] system, an alternating return lifting trap, condensate return pump, or vacuum return pump must be used to force the condensate back into the boiler. In a condensate return pump arrangement, the return piping is arranged for the water to flow by gravity into a collecting receiver or tank, which may be located below the steam-boiler waterline.

CONT

When ... the condensate cannot be returned to the boiler by gravity ... a condensate pump [is used] ... A condensate pump must be located at the low point of return and as close to the boiler as possible.

Français

Domaine(s)
  • Pompes
  • Chauffage
CONT

Dans une telle installation, quand l'eau condensée ne peut retourner par gravité dans le générateur de vapeur, on emploie une pompe refoulante ou une pompe à vide de retour de l'eau condensée, pour introduire celle-ci sous pression dans le générateur. Dans les installations à pompe de retour de l'eau de condensation, la tuyauterie de retour est dimensionnée de manière à ce que l'eau s'écoule par gravité dans le collecteur de retour ou dans la bâche recueillant le produit de condensation

Espagnol

Conserver la fiche 4

Fiche 5 1990-01-23

Anglais

Subject field(s)
  • Heating
OBS

subatmospheric heating system : A system which regulates steam flow into the main throttle valve under automatic thermostatic control and maintains a fixed vacuum differential between supply and return by means of a differential controller and a vacuum pump.

Français

Domaine(s)
  • Chauffage
DEF

[...] chauffage à vapeur fonctionnant dans une installation étanche, sous une pression inférieure à la pression atmosphérique.

DEF

[...] chauffage à vapeur à basse pression dans lequel les tuyauteries n'ont aucune communication avec l'atmosphère.

CONT

Dans les chauffages à vapeur, le fluide véhiculaire utilisé est la vapeur d'eau. La vapeur produite dans les chaudières est conduite jusqu'aux corps de chauffe par un réseau de canalisations, s'y condense en cédant sa chaleur latente de vaporisation et retourne sous forme d'eau aux chaudières, à partir desquelles le cycle recommence. On distingue : - suivant la pression : [...] les chauffages à vapeur à pression sous-atmosphérique [...]

Espagnol

Conserver la fiche 5

Fiche 6 1990-01-23

Anglais

Subject field(s)
  • Heating
CONT

Figure 2 depicts a two-pipe vacuum heating system which uses a condensating pump as a mechanical lift for systems where a part of the heating system is below the boiler room.

Français

Domaine(s)
  • Chauffage

Espagnol

Conserver la fiche 6

Avis de droit d’auteur pour la banque de données TERMIUM Plus®

© Services publics et Approvisionnement Canada, 2026
TERMIUM Plus®, la banque de données terminologiques et linguistiques du gouvernement du Canada
Un produit du Bureau de la traduction

En vedette

GCtraduction (accessible uniquement sur le réseau du gouvernement du Canada)

Utilisez ce prototype d’intelligence artificielle pour traduire le contenu du gouvernement du Canada jusqu’au niveau Protégé B inclusivement. Réservé au personnel de certains ministères et organismes.

Outils d'aide à la rédaction

Les outils d’aide à la rédaction du Portail linguistique ont fait peau neuve! Faciles à consulter, ils vous donnent accès à une foule de renseignements utiles pour mieux écrire en français et en anglais.

Lexiques et vocabulaires

Accédez aux lexiques et vocabulaires du Bureau de la traduction.

Date de modification :