TERMIUM Plus®

La banque de données terminologiques et linguistiques du gouvernement du Canada.

BURNER CONTROLLER [11 fiches]

Fiche 1 2010-07-27

Anglais

Subject field(s)
  • Burners and Steamfitting
CONT

Oil furnace operations have not changed very much. On a call for heat from the thermostat, the burner motor will start. Oil is now pumped to the nozzle, and the ignition transformer is energized. The nozzle is designed to spray the oil into the fire tube as a fine mist. The ignition transformer is designed to create an electrical arc across the electrodes. As the oil mist (also mixed with air) comes in contact with the arc, ignition takes place, and the fire is started.

CONT

Burner controller : The controller is usually located in front of the burner. On a call for heat the controller starts a sequence of events that ensure safe operation before the burner is allowed to start. The controller continues to monitor burner operation while the boiler is running. If for any reason the controller senses an unsafe operating condition it will shut the burner off. Pushing the manual reset on the controller will often restart the boiler.

Français

Domaine(s)
  • Fumisterie et brûleurs

Espagnol

Conserver la fiche 1

Fiche 2 2000-06-30

Anglais

Subject field(s)
  • Burners and Steamfitting
  • Safety Devices (Mechanical Components)
CONT

limit action. The contacts of a limit controller open to shut down a burner(and in some instances make an alarm circuit) because of an abnormal or unsafe condition.

Français

Domaine(s)
  • Fumisterie et brûleurs
  • Organes de sécurité (Composants mécaniques)
OBS

action : Fait de produire un, des effet(s), de modifier des objets (choses, personnes) par son existence, sa présence, son fonctionnement [...]

OBS

Voir la fiche «limiteur / limit; limit controller».

Espagnol

Conserver la fiche 2

Fiche 3 2000-06-20

Anglais

Subject field(s)
  • Heating
  • Burners and Steamfitting
DEF

A system in which the burner is cycled completely automatically under control of an automatic temperature or pressure controller.

Français

Domaine(s)
  • Chauffage
  • Fumisterie et brûleurs

Espagnol

Conserver la fiche 3

Fiche 4 2000-06-02

Anglais

Subject field(s)
  • Control Instrumentation (Mechanical Components)
  • Burners and Steamfitting
DEF

An interlock which proves a condition is proper for burner startup. If it is open, the burner cannot be started. It may be a valve-closed interlock, damper position indicator(low or high fire proving switch), fuel pressure switch, electrical START switch, or oil preheater controller.

Français

Domaine(s)
  • Dispositifs de commande (Composants mécaniques)
  • Fumisterie et brûleurs
OBS

Dérangement : si au démarrage l'allumage n'est pas réalisé à expiration du délai de sécurité [...] le brûleur s'arrête et se met en sécurité.

Espagnol

Conserver la fiche 4

Fiche 5 2000-05-31

Anglais

Subject field(s)
  • Control Instrumentation (Mechanical Components)
  • Burners and Steamfitting
CONT

Manual start. The burner is started by operator action, such as pushing the start button on a controller; sometimes required by local codes to ensure that an operator is actually present at startup.

Français

Domaine(s)
  • Dispositifs de commande (Composants mécaniques)
  • Fumisterie et brûleurs
OBS

Phases du fonctionnement automatique d'un brûleur à fuel : démarrage : mise en route du moteur et du ventilateur; mise sous tension du transformateur d'allumage; après un temps de préallumage de quelques secondes, la vanne magnétique d'admission de fuel s'ouvre et la pulvérisation commence; le brouillard de fuel est amorcé, la flamme brûle; [...]

Espagnol

Conserver la fiche 5

Fiche 6 2000-05-25

Anglais

Subject field(s)
  • Burners and Steamfitting
  • Applications of Electronics
DEF

A controller which positions the firing rate motor to automatically regulate the burner firing rate at a predetermined air-fuel ratio in accordance with load demand. It may position the air and fuel supplies for low fire or for high fire, or it may be a proportioning(modulating) type which gradually varies the air and fuel supplies within limits to meet the load demand.

Français

Domaine(s)
  • Fumisterie et brûleurs
  • Applications de l'électronique
CONT

Le système de surveillance de flamme englobe tout l'appareillage de commande et de sécurité, ainsi que les éléments annexes nécessaires au bon fonctionnement et à la sécurité d'emploi du brûleur dans les conditions prévues d'utilisation. Il comprend donc : [...] un régulateur d'allure de chauffe (firing rate control; firing rate controller), qui règle l'allure de chauffe en fonction de la demande de chaleur, en modifiant le débit d'air ou de combustible.

Espagnol

Conserver la fiche 6

Fiche 7 2000-04-28

Anglais

Subject field(s)
  • Electrical Components
  • Control Instrumentation (Mechanical Components)
  • Safety Devices (Mechanical Components)
DEF

An interlock which proves a condition is proper for burner operation to continue through prepurge, ignition trials, and the run period. It is used with a primary or programming control which will shut down the burner if an improper conditions occurs. The interlock may be a combustion air controller(airflow switch), a damper position indicator(low or high fire proving switch), or a fuel pressure switch. It can be a recycling type, or it may require manual reset.

Français

Domaine(s)
  • Composants électrotechniques
  • Dispositifs de commande (Composants mécaniques)
  • Organes de sécurité (Composants mécaniques)

Espagnol

Conserver la fiche 7

Fiche 8 2000-04-28

Anglais

Subject field(s)
  • Burners and Steamfitting
DEF

A period of time after the run period during which the burner motor (blower or fan) continues to run, driving all the products of combustion and any unburned fuel from the combustion chamber, and supplying air to burn fuel being purged from the fuel line downstream from the safety shutoff valve.

CONT

When the burner is shut off for any reason, the program controller causes the forced draft fan to continue delivering air for a specified time to post-purge the unit of any atomized oil and combustible gases. This post-purge should amount to at least two air changes in the combustion area, gas passages, and breeching.

Français

Domaine(s)
  • Fumisterie et brûleurs
CONT

Les traits communs des systèmes de régulation de grandes chaudières à gaz ou à fuel sont : le système de sécurité de fermeture [...], la vérification de l'allumage électrique avant démarrage, la pré-purge pour évacuer les gaz non brûlés de la chambre de combustion avant démarrage, la post-purge pour exécuter la même opération après l'arrêt et l'allumage à faible intensité [...]

Espagnol

Conserver la fiche 8

Fiche 9 2000-04-28

Anglais

Subject field(s)
  • Safety Devices (Mechanical Components)
  • Burners and Steamfitting
  • Applications of Automation
  • Electrical Components
DEF

A running interlock used with a primary or programming control which will shut down the burner if an improper condition occurs. The control will recycle; it will restart the burner if the condition corrects itself. The interlock is usually a combustion air controller(airflow switch).

OBS

The interlock may be a combustion air controller ..., a damper position indicator ..., or a fuel pressure switch. It can be a recycling type, or it may require manual reset.

Français

Domaine(s)
  • Organes de sécurité (Composants mécaniques)
  • Fumisterie et brûleurs
  • Automatisation et applications
  • Composants électrotechniques

Espagnol

Conserver la fiche 9

Fiche 10 2000-03-31

Anglais

Subject field(s)
  • Burners and Steamfitting
DEF

Provision in a burner for either of 2 firing rates, high or low(no rate in between), selected according to load demand by the firing rate controller. A system is normally wired for guaranteed low fire start.

CONT

Control Valve. Interlocked one lever operation to correctly sequence Vent/Isolate - Available conditions. Self seal couplings prevent spillage during installation and removal of injector. Integral control of Fire/Recirculation and High-Low fire.

Français

Domaine(s)
  • Fumisterie et brûleurs
OBS

Les essais requis sont les suivants : chaudière équipée d'un ou plusieurs brûleurs «à tout ou rien», ou «à tout ou peu», la fonction «peu» étant une phase transitoire du démarrage du brûleur : un essai en période de fonctionnement continu du (des) brûleurs(s); chaudière équipée d'un ou plusieurs brûleur(s) à «tout ou peu», la fonction «peu» n'étant pas une phase transitoire du démarrage du (des) brûleur(s) : un essai à la puissance maximale d'utilisation du (des) brûleur(s) et un essai à la puissance minimale d'utilisation du (des) brûleur(s); [...]

OBS

Voir la fiche «allure maximale / high fire»

Espagnol

Conserver la fiche 10

Fiche 11 2000-02-28

Anglais

Subject field(s)
  • Burners and Steamfitting
DEF

An automatic temperature or pressure sensing device connected in the input circuit of a flame safeguard control. It indirectly acts to turn a burner on or off in order to maintain pressure, air temperature, water temperature, or liquid level within the desired limits.

CONT

Burner controller : The controller is usually located in front of the burner. On a call for heat the controller starts a sequence of events that ensure safe operation before the burner is allowed to start. The controller continues to monitor burner operation while the boiler is running. If for any reason the controller senses an unsafe operating condition it will shut the burner off. Pushing the manual reset on the controller will often restart the boiler.

Français

Domaine(s)
  • Fumisterie et brûleurs
OBS

contrôleur : appareil de réglage, de contrôle.

Espagnol

Conserver la fiche 11

Avis de droit d’auteur pour la banque de données TERMIUM Plus®

© Services publics et Approvisionnement Canada, 2025
TERMIUM Plus®, la banque de données terminologiques et linguistiques du gouvernement du Canada
Un produit du Bureau de la traduction

En vedette

Portail linguistique du Canada

Accédez à une collection de ressources canadiennes sur tous les aspects du français et de l'anglais, y compris des jeux.

Outils d'aide à la rédaction

Les outils d’aide à la rédaction du Portail linguistique ont fait peau neuve! Faciles à consulter, ils vous donnent accès à une foule de renseignements utiles pour mieux écrire en français et en anglais.

Lexiques et vocabulaires

Accédez aux lexiques et vocabulaires du Bureau de la traduction.

Date de modification :